CSB GPL12400 AGM VRLA Battery - GPL Series
CSB's General Purpose Long-Life (GPL) Series batteries are designed to deliver extended service life and exceptional reliability across a broad spectrum of general-purpose applications. Engineered for versatility, the GPL Series is ideal for use in security systems, emergency lighting, medical equipment, and other critical applications. Designed with an emphasis on durability, safety, and energy efficiency, CSB's GPL Series batteries deliver dependable, long-lasting power where consistent performance is essential.
Key Features & Benefits
- Designed for float service power applications
- Design life of up to 10 years in standby service
- Optional flame-retardant case
Applications
- Security Lighting
- Emergency Lighting
- Healthcare Applications
- Medical Devices
- General Purpose
CSB GPL12400 Construction Details
- Valve-Regulated Lead Acid (VRLA) battery
- Maintenance-free, Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%
- Special proprietary formula utilizing 99.99% pure lead ingot in production for lead oxide, lead plate grids, and other lead components
- Pure lead construction and proprietary elements
- Optional flame-retardant case
Specification Details for GPL12400 by CSB Batteries
ATTRIBUTES |
DETAILS |
General Info |
Chemistry |
AGM (VRLA) |
Voltage |
12V |
Capacity |
40Ah @ 20 Hr Rate |
Cells Per Unit |
|
Dimensions
- Overall Length
- Overall Width
- Overall Height
|
7.76 inches / 197.00 mm 6.50 inches / 165.00 mm 6.71 inches / 170.40 mm
|
Weight |
28.48 lbs / 12.92 kgs |
Container Type |
Flame Retardant (94 V-0) available upon request
|
Terminal Type |
|
Terminal Material |
Lead-electroplated pure copper
|
Design Life |
Up to 10 Years in stand-by service at 77°F (25°C) |
Warranty |
1 Year Full |
Electrical Specifications & Performance Characteristics |
Float Charging Voltage |
13.50 to 13.80 Vdc / battery at 77°F (25°C) |
Equalizing Charging Voltage |
14.40 to 15.00 Vdc / battery at 77°F (25°C) |
Maximum Charging Current |
|
Maximum Discharge Current |
|
Internal Resistance |
Approx. 8.5 mΩ |
Operating Temperature Ranges |
Discharge: 5°F to 122°F (-15°C to 50°C)
Charge / Storage: 5°F to 104°F (-15°C to 40°C)
|
Self-Discharge |
Less than 10% after 90 days;
Can be stored for up to 6 months at 77°F (25°C)
Fully recharging is required before usage, and charged sooner if stored at higher temperatures than 77°F (25°C)
|
Electrolyte |
|
Construction Details |
Container |
Flame Retardant (94 V-0) available upon request
|
Cell Cover |
|
Separators |
|
Electrolyte |
|
Safety Valve |
|
Terminal Material
|
Lead-electroplated pure copper |
Certifications & Safety Compliances
- IEC 60896-21/22:2004
- UL1973 Certified
- UL Recognized under UL 1989
- Complies with IATA/ICAO Special Provision A67 for air transport, are classified per MG Amendment 27 as a non-hazardous material for water transport, and recognized by DOT as "Dry Charge" 49 CFR 171-189 for surface transport
- UL Recognized Components
- Optional flame-retardant case
Options & Accessories
- Contact a member of the Power Storage Solutions Sales Team for additional information on options and accessories.
Explore Other Models in the CSB Batteries GPL Series
- GPL1272F2
- GPL12520
- GPL12880
- GPL121000
As your full-service provider, Power Storage Solutions offers more than just products—we provide turnkey installation, system design support, removal and recycling services, and compliance-focused maintenance. Our expert technicians ensure every install is safe, efficient, and built to last. We are proud to offer the following services:
Visit our services page to explore how we can protect your business operations and optimize your critical backup power systems.