SKU: XTV1272F2

CSB Battery XTV Series 12V 6.72 Ah @ 8 Hr Rate Top Terminal F2 Tab AGM VRLA Battery

$30.83

Other models in this line

XTV12200

$76.22

Pre-order

  • Quick Facts

  • Documentation

  • Services

Battery type & OPERATING ENVIRONMENT

AGM (VRLA)
Title
Title

CAPACITY

7.4 Ah @ 20 Hr Rate to 1.75 VPC @ 77ºF (25ºC)

0.82 A Constant Current @ 8 Hr Rate to 1.75 VPC @ 77ºF (25ºC)

6.72 Ah @ 8 Hr Rate to 1.75 VPC @ 77ºF (25ºC)

148 WPC @ 15 Min Rate to 1.67 VPC @ 77ºF (25ºC)

Title

design life & warranty

12 Years Design Life
1 Year Full Warranty
Title

DIMENSIONS

Length: 5.94 in
Width: 2.55 in
Height: 3.88 in
Weight: 5.66 lb
Title

certifications & compliances

49 CFR 171-189, IEC 61056-1/2:2012, UL1973, UL1989, UL-Recognized Component, IATA/ICAO Special Provisions A67
Title

industries

Data Center & UPS, Telecom

Specifications

view more in-depth details on applications & specifications

CSB Battery XTV1272 Specification Sheet.pdf
CSB Battery XTV Installation Operation Manual.pdf
CSB Battery Warranty.pdf
CSB Battery XTV Discharge Tables.pdf
CSB Battery XTV1272 Specification Sheet.pdf
CSB Battery XTV Installation Operation Manual.pdf
CSB Battery Warranty.pdf
Title

safety

view more in-depth details on safety features & certifications 

CSB Battery XTV Safety Data Sheet.pdf

CSB XTV1272 AGM VRLA Battery - XTV Series

CSB's Extreme Temperature Version (XTV) Series batteries are specifically designed to perform reliably in harsh environments, with an operating temperature range of  -4°F to 122°F (-20°C to 50°C). In addition to utilizing pure lead constructions, the XTV Series batteries incorporate an innovative plate design that significantly enhances service life under extreme conditions. A newly developed lead paste formulation further supports stable performance while minimizing the risk of thermal runaway. The XTV Series also offers a smaller volume and lightweight design, with a design life of up to 12 years in standby applications, making it an ideal choice for demanding and space-constrained environments. 

Key Features & Benefits

  • Specifically designed for float service standby power applications in extreme temperatures
  • Design Life of up to 12 years in standby applications
  • Compact and light-weight design
  • Optional flame-retardant ABS case construction

Applications

  • Telecommunications
  • Uninterruptible Power Supply (UPS)

CSB XTV1272 Construction Details

  • Special proprietary formula utilizing 99.99% pure lead ingot in product for lead oxide, lead plate grids, and other lead components
  • Maintenance-free, Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%
  • Valve-Regulated Lead Acid (VRLA) battery
  • Pure lead construction and proprietary elements
  • Optional flame-retardant ABS case construction

Specification Details for XTV1272 by CSB Battery

ATTRIBUTES DETAILS
General Info
Chemistry
AGM (VRLA)
Voltage
12V
Capacity
6.72Ah @ 8 Hr Rate
Cells Per Unit
6
Dimensions
    - Overall Length
    - Overall Width
    - Overall Height

5.94 inches / 150.90 mm
2.55 inches / 64.80 mm
3.88 inches / 98.60 mm
Weight
5.66 lbs / 2.57 kgs
Container Type
ABS (UL 94-HB)
Flame-retardant (94 V-0) available upon request
Terminal Type
Top F2 Terminal - Faston 0.250" Tab
Terminal Material
Lead-electroplated pure copper
Design Life
Up to 12 years in stand-by service at 77°F (25°C)
Warranty
1 Year Full
Electrical Specifications & Performance Characteristics
Float Charging Voltage
13.50 to 13.80V at 77°F (25°C)
Cyclic Charging Voltage
14.40 to 15.00V at 77°F (25°C)
Maximum Charging Current
2.16A
Maximum Discharge Current
130A
Internal Resistance
Approx. 20.40 mΩ
Operating Temperature Ranges
Nominal: 77°F (25°C)
Discharge: -4°F to 122°F (-20°C to 50°C)
Storage: -15°F to 104°F (-15°C to 40°C)
Self-Discharge
Less than 10% after 90 days;
Can be stored up to 6 months at 77°F (25°C);
Fully recharging is required before usage, and charged sooner if stored at higher temperatures than 77°F (25°C)
Electrolyte
Sulfuric Acid
Construction Details
Container
ABS (UL 94-HB) 
Flame retardant (94 V-0) available upon request
Cell Cover
ABS-FR
Separators
AGM
Electrolyte
Sulfuric Acid
Safety Valve
Rubber
Terminal Material
Lead-electroplated pure copper

Certifications & Safety Compliances

  • IEC 61056-1/2:2012
  • UL1973 Certified
  • UL Recognized under UL1989
  • Complies with IATA/ICAO Special Provision A67 for air transport, are classified per MG Amendment 27 as a non-hazardous material for water transport, and recognized by DOT as "Dry Charge" 49 CFR 171-189 for surface transport
  • UL Recognized Components
  • Optional flame-retardant ABS case construction

Options and Accessories

  • Contact a member of the Power Storage Solutions Sales Team for additional information on options and accessories.

    Explore Other Models in the CSB XTV Series

    • XTV12200

    Power Storage Solutions Installation & Services

    As your full-service provider, Power Storage Solutions offers more than just products—we provide turnkey installation, system design support, removal and recycling services, and compliance-focused maintenance. Our expert technicians ensure every install is safe, efficient, and built to last. We are proud to offer the following services: