EnerSys 2ESG-13FR POWERSAFE® ESG BATTERIES
PowerSafe® 2ESG-13FR batteries are engineered with proprietary material and design features that deliver robust performance and reliable service life. This makes the ESG battery ideal for challenging load profiles and service conditions. The five 4 volt (187 - 418 Ah) multi-cell unit construction helps to minimize floor space. All PowerSafe ESG batteries have individual posts for each cell to help ease and simplify the integration
of battery monitoring and test equipment used in routine maintenance and inspections.
PowerSafe ESG batteries have thick positive plates that ensure excellent long discharge capability. Copper insert posts enhance high-rate performance. Individual posts easily accommodate monitoring and test equipment used in routine maintenance and inspections. PowerSafe ESG batteries also employ a Slide-Lock™ post seal that allows for natural plate growth over time, plus a tongue-and groove jar-to-cover seal that provides a robust airtight seal for maximum reliability and reduced maintenance.
2ESG-13FR POWERSAFE® FEATURES AND BENEFITS
• Capacity range 187 - 935 Ah at the 8 hour rate to 1.75 Vpc @ 77°F (25°C)
• 100% initial capacity
• Five multi-cell 4v units (187, 234, 281, 354 and 418) reduces footprint
• Individual terminals to monitor individual cell performance
• Plated copper terminals with dual hole design
• Thick grids provide excellent long duration discharge performance and long life
• 20 year life expectancy in float service at 77°F (25°C) ambient temperature
2ESG-13FR CONSTRUCTION
• 0.28” thick positive plates provide excellent long discharge rates and long life
• Separator – microporous phenolic resin with glass fiber retainers
• Standard jar material Styrene Acrylonitrile (SAN) with flame retardant PVC cover. Optional PC flame retardant jar and cover are available
• Electrolyte – dilute sulfuric acid with specific gravity of 1.215
• Plated copper terminals with dual hole design
• Slide-Lock™ post seal design
• Flame arrestors – included for increased operational safety
2ESG-13FR Installation and Operation
• Tin plated copper inter-cell connectors standard;lead plated optional
• Dual posts for high current carrying capability (ESG-19 and above)
• Excellent one minute rate, long duration discharge and complex duty cycle capability for switchgear applications
• 20 year life expectancy in float service at 77°F (25°C)
• Operating temperature: 32°F (0°C) to 104°F (40°C)
• Recommended temperature: 68°F (20°C) to 86°F (30°C)
2ESG-13FR STANDARDS
• The management systems governing the manufacture of this product are ISO 9001 and ISO 14001 certified
• Optional testing in accordance to IEEE 450 or customer duty cycle available
NOTE: All inter-cell, inter-tier, inter-step, end-to-end inter-rack, back-to-back inter-rack connectors, terminal lugs, and terminal plates are included with every battery. Across-aisle inter-rack connectors are not included
Power Storage Solutions Installation and Service for 2ESG-13FR
We understand that data centers are heavily reliant on batteries for backup power. We also understand that batteries must be redundant and if only one battery in your UPS configuration is not performing; it compromises your overall backup power. Our experience and our focus is to know the batteries and their implication for your operation. To determine the perfect solution, we will partner with you, analyze your critical power needs and construct the backup power solution that will perform as designed.
We can remove and recycle your old battery system then install, properly set up and test your new system. We have been installing stationary batteries for over 20 years. We have the experience, equipment and capabilities to safely perform this type of work.
Routine maintenance ensures your UPS equipment stays reliable, improving your UPS’s overall performance and extending their useful life. Service plans allow customers to be proactive; providing opportunity to detect potential points of failure preventing expensive problems.
When ordering new batteries, also remember to properly recycle your old lead batteries. Federal and state regulations require lead-acid batteries be recycled. Power Storage Solutions’ nationwide service organization can arrange pickup, transportation to and recycling at any one of our company affiliated smelters. Click Here for More Information
For More Information from EnerSys Website: EnerSys PowerSafe ESG
Additional Information
Weight | 177 lbs |
---|---|
Length | 9.2 |
Width | 11.1 |
Height | |
Brand | Enersys |
Battery Model | PowerSafe ESG |
Equipment | Batteries |
Market | Switchgear |
EnerSys PowerSafe ESG Flooded Batteries Engineered for the demanding Utility Market. Call Today. Free Quote. Services: Installation, Service