POWER IS AT THE CENTER OF EVERYTHING WE DO

EnerSys DDmP100-21 POWERSAFE® DDmP BATTERIES

PowerSafe® DDmP100-21 batteries deliver an ideal solution for long life, larger capacity valve regulated lead-acid (VRLA) battery requirements.  All PowerSafe DDmP batteries feature a steel can (module) design with integral racking system choices. PowerSafe DDmP batteries provide a cost-effective battery system for compact, quick and simple installations.  EnerSys PowerSafe® DDm DDmP100-21 battery, with its optimized recombination technology and extra thick plates, provides excellent performance and service life across a wide range of applications including: telecommunications, power generation/distribution sites, and UPS.

DDmP100-21 POWERSAFE® FEATURES AND BENEFITS

• Capacity range 105 - 2000Ah
• Lead-calcium alloy
• Valve regulated design with recombinant technology eliminates watering requirements
• Flame retardant polypropylene jar and cover (UL94 V-0 LOI 28%)
• Module design allows for easy, fast installation, uniform and consistent compression, along with built in cell protection

DDmP100-21 POWERSAFE® APPLICATIONS

  • Macro Cells
  • Central Offices/Switching Centers
  • Energy Storage
  • Switchgear and Substation
  • Industrial UPS
  • Data Centers

DDmP100-21 POWERSAFE® CONSTRUCTION

• Positive plate – thick 0.252” lead-calcium-tin grids minimize corrosion and prolong life
• Negative plate – balanced lead-calcium grids optimize recombination efficiency
• Absorbed Glass Mat (AGM) separator - mechanically strong, low electrical resistance, absorbed glass mat, which completely absorbs the electrolyte into its structure
• Container/cover - standard UL94 V-0 flame retardant polypropylene (LOI 28%)
• Terminal post – square lead-tin coated copper insert cross-drilled (0.25” holes) with large surface area, to provide maximum conductivity; 2DDm35-07 has round receptacle for 1/4-20 hardware.
• Terminal seal – ring burn with secondary epoxy resin seal is 100% water bath tested in the factory and proven in service
• Relief valve – operates at 2-3 psi and is complete with integral flame arrestor

DDmP100-21 POWERSAFE® Installation and Operation

• Compact, quick and simple installation process
• Low maintenance – no watering required
• Thick plates, single piece container construction, robust construction for long life
• Welded/epoxy dual post seal design means zero leaks
• 100% “out of the box” initial capacity
• Operating temperature: -4°F (-20°C) to 122°F (50°C) Recommended temperature: 68°F (20°C) to 86°F (30°C)
• Initial post torque 85 in - lb (7.1 ft - lb), 9.6 Newton meters (N-m) Re-torque to 80%; 2DDm35-07 post torque 60 in - lb (5 ft - lb), 6.8 N-m

DDmP100-21 POWERSAFE® STANDARDS

• Non-spillable classification (UN2800)
• Approved for air transportation (IATA A67)
• Recognized by UL (UL standard 1989)
• The management systems governing the manufacture of this product are ISO 9001:2008 and ISO 14001:2004 certified
• Cell is NEBSTM certified

Power Storage Solutions Installation and Service for DDmP100-21

We understand that data centers are heavily reliant on batteries for backup power. We also understand that batteries must be redundant and if only one battery in your UPS configuration is not performing; it compromises your overall backup power. Our experience and our focus is to know the batteries and their implication for your operation. To determine the perfect solution, we will partner with you, analyze your critical power needs and construct the backup power solution that will perform as designed.

We can remove and recycle your old battery system then install, properly set up and test your new system. We have been installing stationary batteries for over 20 years. We have the experience, equipment and capabilities to safely perform this type of work.

Routine maintenance ensures your UPS equipment stays reliable, improving your UPS’s overall performance and extending their useful life. Service plans allow customers to be proactive; providing opportunity to detect potential points of failure preventing expensive problems.

When ordering new batteries, also remember to properly recycle your old lead batteries. Federal and state regulations require lead-acid batteries be recycled. Power Storage Solutions’ nationwide service organization can arrange pickup, transportation to and recycling at any one of our company affiliated smelters. Click Here for More Information

For More Information from EnerSys Website: EnerSys PowerSafe DDmP